Overview

Carel replacement DPDC110000 Humidity Sensor. Duct Sensor TEMP. -10T60GR.C. (OUT 0-1VDC - 4-20MA) / HUMID. RH 10-90% (OUT 0-1VDC - 4-20MA)

The DP* series temperature and humidity sensors represent the latest version of the CAREL sensors for rooms, industrial environments and ducts, developed for the residential and light industrial HVAC/R market, with the quality that CAREL stands out for. The range includes models with 0 to 10 V output and with RS485 serial output (Carel or Modbus). The DP* series sensors use sensors with a digital output, and feature a wider temperature and humidity range than the previous models, ensuring all the versatility required by the applications in the specific market, with excellent and quality/price ratio. These sensors are typically used together with the Carel controllers however, they can also be used with third-party devices.

Features:

The CAREL electronic temperature and/or humidity sensors have been developed for applications in the heating, refrigeration and air-conditioning sectors.

The following models are available: a) wall, b) industrial environment, c) duct. The various models differ due to the different active outputs (current or voltage, selectable by jumpers) except for the models with NTC resistive temperature output (hereinafter indicated as “NTC res.”), compatible with CAREL controllers. A model is also available with optically-isolated RS485 serial output for connection to the serial line (pCO or Carel supervisor). The sensors can have an alternating current (12 to 24 Vac) or direct current (8 to 32 Vdc) power supply.

Wall sensors (DPW*): These are used in heating and air-conditioning systems. Their design makes them suitable for use in the home. Ready for wall-mounting.

Sensors for industrial environments (DPP*): These are used in industrial environments (cold rooms, pools etc.) where a high index of protection is required, both for the case (IP55) and the
sensors (IP54). Ready for wall-mounting. 

Duct sensors (DPD*): These are used in ducted heating and air-conditioning systems. Supplied together with a fastening bracket.

Maintenance:

When cleaning the instrument do not use ethyl alcohol, hydrocarbons (petrol), ammonia and derivatives. Use neutral detergents and water. Periodically
check the aeration slits on the sensor to make sure that air can flow freely through, without obstructions due to impurities or dust in the site of
installation.

Specifications

More Information
Manufacturer Carel
Product Type Humidification
Product Length 13.400
Product Width 4.700
Product Height 4.000
Product Weight 0.485
Dimension Length 14.250000
Dimension Width 5.850000
Dimension Height 5.650000

Documentation